Boiler Efficiency Optimisation

Supervising control software module is intended to adjust boiler operating conditions in order to ensure its efficiency. The module employs an algorithm with built-in optimizing procedure, which establishes boiler control system presets and effects recommended changes.

The module is installed on a workstation, which additionally runs the boiler efficiency calculator module and the combustion optimisation module. The supervising control module generates presets for various boiler controllers .

 

The software module processes the following values from the existing control system :

  • rotating speeds of coal conveyors, whereas the total rotating speed is always fixed and equal to the controller- or operator preset load value
  • pulveriser sifters (dust separators) baffle positions
  • preset temperatures for mix after the pulveriser
  • secondary air for dust burners baffle positions
  • preset oxygen level for the boiler’s air supply regulator.

 

 

IBoiler efficiency optimizer’s operator interface

 


Other factors affecting boiler efficiency and the following parameters, which limit other values’ variation ranges are also taken into consideration:

  • current steam temperature
  • combustion gases temperature transverse asymmetry (i.e. combustion gases temperature difference between the left and the right side
  • pulveriser motor current
  • carbon oxide levels in combustion gases
  • nitrogen oxide levels in combustion gases
  • pressure of air supplied to the boiler
  • boiler load
  • operating pulverisers configuration
Basing on measured current values of these parameters, the value of heat losses and indications for their reduction are established.